Average Rating: n/a

Specs
| Item | Line Voltage Monitor |
|---|---|
| Type | Manual or Automatic Reset |
| Control Volts | 24-240 |
| NC Output (Amps) | 10 |
| N.O. Output (Amps) | 10 |
| Contact Rating (Amps) | 10 |
| Voltage | 80 to 300 |
| Phase | Single |
| Hz | 50/60 |
| % Volts Unbalance | 5 to 25, Adj. |
| Time Delay | Adj. 0 to 720 Sec. |
| Response Time (ms) | 0.1-10 Sec. |
| Temp. Rating (F) | -40 To 167 |
| Memory Storage | Programmable 25-Fault |
| Monitors | Voltage Unbalance, High/Low Voltage |
| Depth | 3" |
| Height | 1-3/8" |
| Width | 3-1/4" |
| Application | HVACR |
| For Use With | 1 Phase Equipment |
| Agency Compliance | UL,cUL |
| Includes | LCD Display |
| UNSPSC | 39121517 |
| Weight | 0.500000 |
| SKUs | 5KPX9 |
Description
- Built-in antishort cycle protection helps prevent rapid system recycling. Detects high/low voltage conditions. Interrogation delay prevents nuisance trips. 3UW94 has LEDs to indicate fault and normal conditions. 5KPX9 has backlit display.
- Output: relay SPDT, 5A for 3UW94, and 10A for 5KPX9