Average Rating: 5

Specs
| Item | Line Voltage Thermostat |
|---|---|
| Type | Heating/Cooling |
| Switch Type | SPDT |
| Switch Action | Open / Close on rise |
| Number of Switches | 1 |
| Control Range (F) | 44 to 86 |
| Differential (Deg. F) | 2 |
| Height (In.) | 4-1/2 |
| Width (In.) | 2-15/16 |
| Depth (In.) | 1-1/2 |
| Sensor Type | Dual Diaphragm |
| Characteristics | Light Duty |
| Color | Beige |
| Application | Heating and Cooling |
| Display | Analog |
| Voltage Range | 120 to 277VAC |
| Cooling Full Load @ 120V | 8 |
| Cooling Full Load @ 240V | 4 |
| Cooling Locked Rotor @ 120V | 48 |
| Cooling Locked Rotor @ 240V | 24 |
| Full Load Amps @ 120V | 8 |
| Full Load Amps @ 240VAC | 4 |
| Locked Rotor Amps @ 120V | 48 |
| Locked Rotor Amps @ 240V | 24 |
| Contact Rating Resistive @ 120V (A) | 22 |
| Contact Rating Resistive @ 240V (A) | 22 |
| Pilot Duty Contacts (VA) | 125 |
| Mounting | Standard 2 x 4" Vertical or Horizontal Box |
| Includes | Vertical scaleplate with thermometer, horizontal scaleplate with no thermometer, range stops and locking screws, wall plate |
| Agency Compliance | UL File No. E47434, Guide No. XAPX., CSA Certified, File No. LR1322 |
| UNSPSC | 41112209 |
| Weight | 0.500000 |
| SKUs | 4NE56, HONT651A3018, 157766, T651A3018 |
Description
- Hazardous Material
- Mount to standard 2" x 4" vertical box. UL Listed, except 4NE56. Additional agency standards as noted.
- 4NE56
- Features 44 F frost protection setting.
Customer Reviews
T651A
Monday, April 30, 2012The experience was good, not too thrilled with the product it self, but not too many choices to replace this type of thermostat, it does not have an an ON-OFF switch to turn the system off when you are out of town for a prolonged period of time, also wish there could be a digital replacement.