Average Rating: n/a

Specs
| Item | Clamp-On Power Meter Kit |
|---|---|
| Max. Watts | 1200kW |
| Max. VA | 1200kVA |
| Power Accuracy | +/-2.5% Rdg + 5 Digits |
| Max. AC Amps | 1400 |
| Max. DC Amps | 2000 |
| Current Accuracy | +/-1.5% Rdg + 5 Digits |
| Max. AC Volts | 825 |
| Max. DC Volts | 825 |
| Voltage Accuracy | +/-3% Rdg + 5 Digits |
| Power Factor | 0.3 to 0.99 |
| Crest Factor | 1.1 to 3 |
| Calibration Frequency | 15 to 1000 Hz |
| Jaw Opening | 2.4" |
| True RMS | Yes |
| Data Logging | 150,000 Readings |
| Operating Temp. Range | 32 Degrees to 122 Degrees F (0 Degrees C to 50 Degrees C) |
| Display | Color LCD |
| Phase | 1 |
| Safety Rating | CAT IV 600V |
| Power Source | (2) AA Batteries |
| Includes | Soft Carrying Case, 2 Voltage Leads and Clips, Universal AC Adapter, Data Logging Software, Battery Pack and Instructions |
| Manufacturers Warranty Length | 1 Year |
| UNSPSC | 41113648 |
| Weight | 7.500000 |
| SKUs | 1FBK2 |
Description
- Rugged, reliable tools test11 power quality for troubleshooting, preventive maintenance, and analysis in industrial applications and utilities. NIST Certified models have NIST in Mfr. Model
- Fluke 345 Power Quality Clampmeter
- AC/DC current: Clamp-on measurement of AC current up to 1400A RMS and DC current up to 2000A without breaking the circuit Highest safety rating: Cat IV 600V rated for use at the service entrance Accurate in noisy environments: Even with distorted waveforms present on electronic loads with low-pass filter Data logging: Identifies intermittent faults by logging any power parameters, including harmonics, for minutes or months Troubleshoots harmonics: Analyzes and logs harmonics digitally or graphically Inrush current: Captures and analyzes nuisance tripping, from 3 to 300 sec. View graphs and generate reports with included PowerLog software