Average Rating: n/a

Specs
| Item | Automatic Standby Generator |
|---|---|
| Engine Cooling Method | Liquid |
| kW | 130 |
| kVA Rating | 162.5 |
| Voltage | 277/480 |
| Height | 55" |
| Length | 116" |
| Enclosure Material | Aluminum |
| Fuel Type | Propane |
| Engine Brand | Generac |
| Engine Size | 6.8L |
| Engine RPM | 3000 |
| Amps | 195.6 |
| LP Consumption @ Half Load | 19.56 gph |
| Hz | 60 |
| Sound Level dBA | 65 |
| Automatic Volts Regulation | Yes |
| 12VDC Battery Charger | Yes |
| Battery Requirements | 24F |
| Engine (Block Heater) | Optional |
| Fault Indicator Lights | Yes |
| Fuel NPT Pipe Connection Sz. | 1-1/4" |
| High Temp. Alarm | Yes |
| Low Coolant Level Alarm | Yes |
| Low Oil Pressure Alarm | Yes |
| Main Circuit Breaker | Yes |
| Min. Gas Pressure @ Generator (In WC) | 5 to 14 |
| Over Crank Protection | Yes |
| Phase | 3 |
| Power Factor | 0.8 |
| Repeat of Exercise Cycle | 7 |
| Run Time Hour Meter | Yes |
| Over Speed | Yes |
| Includes | Oil Drain Extension, Radiator Drain Extension, Battery Cables and Rack, Flex Fuel Line, Fan and Belt Guards, Instruction Sheets |
| Standards | UL cUL, CSA, NEMA, EGSA |
| UNSPSC | 26111604 |
| Weight | 2899.000000 |
| SKUs | 2ZNU2 |
Description
- This item has been restricted from sale in the following states: [CA]
- California Proposition 65 Warning: This product contains a chemical known to the State of California to cause birth defects or other reproductive harm.
- Shut down automatically for low coolant level, high coolant temperature, and low oil pressure. Feature crank timer, runtime hour meter, cool flow radiator, watertight electrical connections, and closed coolant recovery system. UV- and ozone-resistant hoses. Mainline circuit breaker. Solid-state frequency compensated voltage regulator. All input connections are in a single area. Models equipped with aluminum housing are designed to withstand highly corrosive environments. Require local permits for gas piping, concrete foundation, and electrical inspection and approval. Additional standby generators are available; contact your local branch. On DrillSpot.com , search for "standby generators."
- UL 2200 Listed, CSA Certified.
- Min. battery requirement: 525 CCA Clean, consistent power output for sensitive electronics Automotive-grade liquid-cooled engines Quiet-Test low speed weekly exercise mode Require RTS Series transfer switch, sold separately on page 1361, 1362 60 Hz