Circuit Breaker, C Curve, Standard Circuit Breaker Type, Number of Poles 2, Voltage 240VAC, Amps 2, Single Phase, Min Wire Size 18 AWG, Max Wire Size 4 AWG, Length 4.21 In, Width 1.42 In, Depth 3.00 In, Box Lug Terminal Connection, Frame Size 35 Amp/C60N, Max DC Voltage 125 V, Standards UL Listed/CSA Certified/IEC Rated
Miniature Circuit Protectors and Breakers- UL 489 Branch Circuit Protection
- Listed for branch circuit protection when protecting the conductor to the equipment. Also IEC 60947-2.
- Multi 9 breakers feature factory-calibrated overload curves. Withstand 6000V impulse. Rated for 20,000 tripping operation cycles. Line and load side box lug terminals (pressure plate type) are suitable for use with multiple wires. DIN rail or panel mount with accessory front bracket. Wire size: max. 4 AWG Cu for 0.5 to 25A models, max. 2 AWG Cu for 30 to 63A models.
- 10kA IR at 240VAC
- B curve = magnetic trip between 3.2 and 4.8 times rated current (computer, electronic, and generator applications) C curve = magnetic trip between 7 and 10 times rated current AC and 7 to 14 times for DC (general purpose applications) D curve = magnetic trip between 10 and 14 times rated current (motors, transformers, and similar applications)